To: "Ryman, Michael G." <Michael.Ryman@montgomerycountymd.gov>, "Neubauer, Steven" <Steven.Neubauer@montgomerycountymd.gov>, "Wolff, Steve" <Steve.Wolff@montgomerycountymd.gov>, "Krouse, Ernest" <Ernest.Krouse@montgomerycountymd.gov>, "Neubauer, Steven" <Steven.Neubauer@montgomerycountymd.gov>, "Dean, Daniel J." <Daniel.Dean@montgomerycountymd.gov>
Subject: FMRS: New Apparatus Defect Report for Stock #1-08-9038

This is to inform you that Christopher Reilly reporting from station 15 has submitted the following defect report for Stock #1-08-9038.

Defect Description: Annual Pump test today: Dry prime results- primer activated for 39 seconds to achieve 20"HG after 5 minutes the reading was 17". Vac leak detected at the water strainer ( adjusted the gasket ) and the officer side high flow discharge. Hard sleeves were utilized from the unit, the unit obtained and maintained a draft without issue. The pressure governor operated as designed. Nothing to note with the performance test, testing pressures performed in the volume mode.
Is Out Of Service? No
Work Order# 119186

Please click here to log into the Fleet Management Reporting System.